Line Bushings
Line bushings are used to electrically connect equipment in potentially explosive atmospheres. The connection is established either between a flameproof enclosure and an enclosure of another type of protection and in accordance with DIN EN 60079-0. Alternatively, two flameproof enclosures are connected. Thus cables are protected from direct contact.
Varying designs, line bushings can be used in intrinsically safe areas for measuring, control or energy limited circuits.
Line bushings that do not feature cables, i. e. they are only cast, can be used to seal flameproof enclosures (Ex “d”). also through a line bushing, entries or threads can be closed off and if the system needs to be extended at a later date then line bushings containing cables can replace the existing, sealed ones. The full range is covered by the following organisations.

IECEx, GOST, CSA, CSA-US,FM(in accordance to UL-standards)
NB. For ATEX we can offer apparatus 'X'-approval, meaning you can use line bushings in existing products without a re-approval of your product.
Types of line bushings

Line bushings are available in two types: screw in and plug in.
The default sizes of screw in line bushings range from M10 to M42. If other sizes are required for Ex use then they will require additional certification. With the plug in variant, sizes are adjusted to those of common sockets.
An essential feature of line bushings is the high adhesion of cast resin on cables.
In this aspect, we do not compromise and Radox cables are high-temperature resistant and proved to be very adhesive and the cast resin used is a certified future-proof cast resin.
Here is a list of our approved range of wires and cables:
Cable Name | Type | Temperature Range |
Radox 125 | wires | -50°C to 115°C |
Radox 155 | wires | -55°C to 100°C |
JZ-500 Helu | wires | -40°C to 80°C |
H05V-K | cable | -30°C to +80°C |
H07G-K | wires | -40°C to 110°C |
H07RN-F | wires | -30°C to 60°C |
INSGAF-OU (3kV) | wires | -40°C to 80°C |
Betatherm 145 | wires | -55°C to 115°C |
FBL Typ 14 x0,08 | flat ribbon cable | -20°C to 105°C |
G50/CWJH D20 | fibre optic multi mode | -20°C to 70°C |
G50/CWJH D27 | fibre optic multi mode | -20°C to 70°C |
E9/CWJH E30 | fibre optic single mode | -20°C to 70°C |
Balzertherm 110HX | wires | -40°C to 110°C |
specialcable 2 x AWG 28/7 | twisted pair | -55°C to 105°C |
Metrofunk Kabelunion | strands 0,09mm² | -40°C to 105°C |
RG174 U | coax cable | -35°C to +80°C |
Customised Ex & Industrial Line Bushing Solutions

If our standard application does not cover your requirement, again at indEx and our partners, we can use our extensive expertise to come up with a customised solution which is cost effective, safe, efficient and reliable and also help with industrial solutions such as high temps, pressure etc.

LBP – Ex approved pluggable line bushings
- Wide temperature range
- Ready to use
- Many International approvals
- No re-certification required
Line bushings are used to electrically connect equipment in potentially explosive atmospheres. The connection is always made between a flameproof enclosure (Exd) and an enclosure with a different type of protection in accordance with IEC 60079-0. Alternatively, two flameproof enclosures are connected. Therefore the cables are protected from direct contact.
Depending on the design, line bushings can be used for intrinsically safe, measurement, control or power circuits, or combinations of the above.
All line bushings are cast with high temperature and leakage current resistant resin to isolate them from the enclosure. Ideal for any application.
Applications
- Ex d enclosures, housings or Pumps
- Sensors, measurement devices, motors, actuators, pneumatic and hydraulic devices, etc.
- Used on Sea-platforms, Drilling Rigs, rolling mills, gas tanks, climatic chambers, compactors, etc.
Approvals
- Ex II 2G Ex db IIC T4/T5/T6
- Ex II 2D Ex db IIIC T135°/T100°C/T85°C
- Ex I M2 Ex d I Mb
Approval Bodies
ATEX, IECEx, GOST, CSA
Technical Data
Voltage: | 440V, 690V, 1000V, 3000V, 6000V (depending on the model type) |
Conductor sizes: | 0,07mm2 to 185mm2 |
Temperature range: | -55°C...115°C (depending on the model type) |
Max. conductor quantity: | up to 50 wires |
Bushing: | Ø10mm to Ø40mm |
Bush length: | >10mm |
Bushing material: | Nickel-plated Brass (other materials on request) |
Standard cable material: | RADOX 125 (other materials on request) |

LBSM – Ex approved threaded line bushings
- Wide temperature range
- Ready to use
- Many International approvals
- No re-certification required
Line bushings are used to electrically connect equipment in potentially explosive atmospheres. The connection is always made between a flameproof enclosure (Exd) and an enclosure with a different type of protection in accordance with IEC 60079-0. Alternatively, two flameproof enclosures are connected. Therefore the cables are protected from direct contact.
Depending on the design, line bushings can be used for intrinsically safe, measurement, control or power circuits, or combinations of the above.
All line bushings are cast with high temperature and leakage current resistant resin to isolate them from the enclosure. Ideal for any application.
Applications
- Ex d enclosures, housings or Pumps
- Sensors, measurement devices, motors, actuators, pneumatic and hydraulic devices, etc.
- Used on Sea-platforms, Drilling Rigs, rolling mills, gas tanks, climatic chambers, compactors, etc.
Approvals
- Ex II 2G Ex db IIC T4/T5/T6
- Ex II 2D Ex db IIIC T135°/T100°C/T85°C
- Ex I M2 Ex d I Mb
Approval Bodies
ATEX, IECEx, GOST, CSA
Technical Data
Voltage: | 440V, 690V, 1000V, 3000V, 6000V (depending on the model type) |
Conductor sizes: | 0,07mm2 to 185mm2 |
Temperature range: | -55°C...115°C (depending on the model type) |
Max. conductor quantity: | up to 50 Strands |
Thread: | M10 to M42 |
Thread length: | >10mm |
Bushing material: | Nickel-plated Brass (other materials on request) |
Standard cable material: | RADOX 125 (other materials on request) |
Questions, enquiries?
Call us on +44 (0)1233 801890 or email sales@indexenclosures.com